Excerpt

Valve Seating Test

 This tests that the Genius Radiator Valves have been mounted correctly

  1. On the app, override one zone to 28°C for 1 hour. Ideally choose a room that has only 1 Radiator Valve. 

    1. Click on the zone to override.
    2. Change the mode icon at the top-right to the Override symbol (3 arrows).
    3. Ensure the override temperature is 28°C and the override duration should be 1 hour.
  2. Check that the Receiver Unit is active:
    1. A Single Channel Receiver shows a green light.


      Pagebreak

    2. Hold down the Heating button on the the Dual Channel Receiver (the light at the top-left with turn green for 2 seconds).
    3. An Electric Switch shows a red light next to 'HUB'.
  3. Check the boiler fires as normal and the correct zone valve has opened or pump has come on.
  4. Check that the central heating pipe from the zone valve, pump or boiler gets hot.

  5. Wait 10 minutes!

  6. Now check the radiator in & out pipes and that each radiator is cold not hot! (Except for the overridden zone).

    Info

    This confirms all the valves are properly seated on the radiators, and they can turn the radiators off.


Underfloor & Electric Heating Test

...

  1. Override all of the heating zones to 28°C.

    1. Click on the 'My House' icon at the top left.

      Pagebreak

    2. Tap 'Override' at the bottom of the screen.
    3. Choose 'Select all'.
    4. Ensure the override temperature is 28°C and the override duration should be 1 hour.
  2. Check all the rooms receive the new set point temperature on the app. Each zone will have 'Set: 28'.
  3. You must wait 10 minutes! 
  4. All of the valves will wake up on their own and get the message to go to 28ºC.
  5. Make sure the radiator valves have received the message by pressing any of the three buttons button to light up light up the screen. Each valve should read the Override temperature, i.e. 28ºC.

    Info
    • This confirms all of the valves have good communication with the Genius Hub.
    • The radiators DO NOT need to warm up. The valves can take up to 1 hour to react when newly installed as they learn how far the pin needs to be opened.


...