This tests that the Genius Radiator Valves have been mounted correctly
On the app, override one zone to 28°C for 1 hour. Ideally choose a room that has only 1 Radiator Valve.
A Single Channel Receiver shows a green light.
Hold down the Heating button on the the Dual Channel Receiver (the light at the top-left with turn green for 2 seconds).
Check that the central heating pipe from the zone valve, pump or boiler gets hot.
Wait 10 minutes!
Now check the radiator in & out pipes and that each radiator is cold not hot! (Except for the overridden zone).
This confirms all the valves are properly seated on the radiators, and they can turn the radiators off.