None of the rooms of the house need heat, whole house on the app us blue, but the boiler is still firing unnecessarily. Some combination boilers (made by companies like Vaillant and Worcester Bosch) have a setting where the boiler could be set to maintain hot water in the system for the taps. For example, this boiler can have two programs, one for heating and one for hot water built into the front of the boiler. The heating program needs to be left on 24/7 as this is being controlled by the Heat Genius system via the thermostat terminals on the boiler. However, if the hot water timer is left on, it will cause the boiler to come on intermittently during the day, because a thermostat in the small hot water cylinder in the back of the boiler is triggering the boiler to make more hot water. When this timer is turned off for the hot water the boiler will stop turning on intermittently to heat this water, but the boiler will still provide hot water on demand.
Skip to end of banner
Go to start of banner
The boiler is firing, even though there's no demand for heat